50
A. EF ABN.STOP external fault 90 Warning: external error. This will be shown on Quick Stop
condition.
A.ndOH no A. drive overheat 91 Warning: no more overtemperature of motor TEMPERATURE
SENSOR. Motor SENSOR is low-resistance again.
A.nOHI no A.STOP overheat int. 92 Warning: no more overtemperature in the interior
A.buS ABN.STOP bus 93 Warning: Watchdog for communication between operator/
control card has responded
A.PRF ABN.STOP prot. rot. for. 94 Warning: locked direction of rotation clockwise
A.PRR ABN.STOP prot. rot. rev. 95 Warning: locked direction of rotation counterclockwise
A.dOH ABN.STOP drive over heat 96 Warning: overtemperature of motor TEMPERATURE SENSOR
A.OH2 ABN.STOP motor protect. 97 Warning: electronic motor protective relay has tripped
A.nOL no ABN.STOP overload 98 Warning: no more overload, OL counter has reached 0 %.
A. OL ABN.STOP overload 99 Warning: Overload can only be reset at A.nOL, if OL counter
has again reached 0 %
A.OL2 ABN.STOP overload 2 100 Warning: Overload can only be reset at A.nOL2, if cool-down
time has elapsed
A.nOL2 no ABN.STOP overload 2 101 Warning: no more overload, the cool-down time has elapsed.
A.SET ABN.STOP set 102 Warning: set selection: It has been attempted to select a
locked parameter set.
Error Diagnosis
Commentaires sur ces manuels